The FBI and EPA say attackers have remotely altered internet-facing Rockwell Automation MicroLogix 1100 and 1400 controllers at water and wastewater utilities in at least seven states since July 27. The actors changed controller IP addresses and passwords, causing loss of monitoring and, in some cases, control. Reported effects included pressure loss and flooding. The agencies have not identified the utilities, an actor, or an exploit chain.
At least one organization found modified PLC project files after noticing ladder-logic differences across several sites. Similar third-party network setups appeared across multiple victims, which the agencies say may have multiplied the attackers’ success.
Inventory every MicroLogix 1100 and 1400, including units behind cellular modems. Remove direct internet exposure, require a monitored gateway, allow only expected control-system communication, and replace credentials. Compare the running project, ladder logic, and input/output configuration with a known-good source. Review retained PLC, modem, HMI, and workstation evidence before placing a validated controller in Run or Hard Run.
Verify that public access is gone, allowlists match the approved architecture, and logic matches the trusted baseline. Investigate unexplained access on connected devices and have operators demonstrate safe manual control. Missing retained baselines or logs leave the investigation open.